Investigation and Analysis of Ice and Snow Disaster Suffered by Hunan Power Grid in 2008

在线阅读 下载PDF 导出详情
摘要 InJanuary2008,asuddendisastercausedbyicingandsnowinghappenedinlargeareasofCentralChinaandSouthChina.TheequipmentsofHunanpowergridwereseriouslydamagedduringtheicingandsnowingdisaster.AnexpertgroupfromChinaElectricPowerResearchInstitute(CEPRI)wasorganizedandwenttoHunanprovinceforfieldinvestigation.Asasummaryofthisinvestigation,thispaperintroducespowerequipmentdamages,suchasflashovercausedbyicing,collapseoftowers,conductorbreakageanddamageofsubstationequipments.Thecountermeasuresadoptedforthisicingandsnowingdisasterarealsosummarized.Theanalysisshowsthattheraremeteorologicalconditionisthemainreasonforlarge-areadamageofHunanpowergrid.IntheicingdisasterofHunanpowergrid,theicethicknessgreatlyexceedsthepermissiblelimitofdesign,thusitisnecessarytoimprovethedesignparametersreasonablytoagainsticingoftransmissionlines,andthedesignofexternalinsulationandtheanti-icingtechnologyforsubstationsarealsoneedtobeenhanced.
作者
机构地区 不详
出处 《电气:英文版》 2008年4期
关键词
出版日期 2008年04月14日(中国期刊网平台首次上网日期,不代表论文的发表时间)